Type Height Dia Mass Empty Mass Full Charge
5kg Steel Alloy 750mm 138mm 10.5 KG 15.5 KG 5 KG
2kg Steel Alloy 580mm 105mm 5.6 KG 7.6 KG 2 KG
5kg Aluminium 700mm 151mm 7.3 KG 12.3 KG 2 KG
2kg Aluminium 500mm 117mm 3.3 KG 5.3 KG 2 KG

 

Type Working Pressure Test Pressure Burst Pressure Safety Valve
5kg Steel Alloy 6000kPa at 20°C 25000kPa >45000kPa Burst Disc
2kg Steel Alloy 6000kPa at 20°C 25000kPa >45000kPa Burst Disc
5kg Aluminium 6000kPa at 20°C 21500kPa >21500kPa Burst Disc
2kg Aluminium 6000kPa at 20°C 21500kPa >21500kPa Burst Disc

 

Type Fire Rating Effective Range Discharge Time Filling Ratio Approval
5kg Steel Alloy 34B 4m 13sec 0.66 SANS1567
2kg Steel Alloy 8B 3m 8sec 0.66 SANS1567
5kg Aluminium 34B 4m 13sec 0.66
2kg Aluminium 8B 3m 8sec 0.66